HTW-1260 T5
1260 kVA Generator set Open Skid
Powered by: MITSUBISHI
Alternator: STAMFORD
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 1080kW prp ; 1190kW standby
- Manufacturer: MITSUBISHI
- Model: S12R PTA
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 12-V
- Bore and Stroke: 170 x 180 mm
- Displacement: 49,03 L
- Cooling System: Water
- Lube Oil Specifications: API CD or CF SAE 30 or SAE 40
- Compression Ratio: 14,0:1
- Fuel Consumption ESP: 287,92 l/h
- Fuel Consumption 100% PRP: 261,31 l/h
- Fuel Consumption 75 % PRP: 201,75 l/h
- Fuel Consumption 50 % PRP: 146,03 l/h
- Fuel Consumption 25 % PRP: 89,67 l/h
- Lube oil consumption with full load: 0,8
- Total oil capacity including tubes, filters 180 L
- Total coolant capacity: 335 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 304 mm
- Oil temperature sensor
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: S6L1D.G4
- Poles: 4
- Connection type (standard): Star
- Mounting type: S-00 21"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Double drive-shaft
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Water Jacket Heater with single phase pump
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 520 ºC
- Exhaust Gas Flow: 258 m3/min
- Maximum allowed back pressure: 600 mm H2o
- Heat dissipated by exhaust pipe: 587,17 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 5880 m3/h
- Cooling Air Flow: 30 m3/s
- Alternator fan air flow: 1,95 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 x 2 kW
- Starting power: 10,2 x 2 CV
- Recommended battery: 400 Ah
- Auxiliary Voltage: 24 Vdc
- Starter current peak: 1250 A
- Nominal starter current: 400 A
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 75 mm Hg
- Maximum return feed pump: 150 mm Hg
- - DIMENSIONS.
- Length: 4.592 mm
- Height: 2.398 mm
- Width: 2.200 mm
- Maximum shipping volume: 24,23 m3
- Weight with liquids in radiator and sump: 9.550 kg
Power
kVA
1260
1345
Prime power (670 - 2555)
Stand by (735 - 2816)
Stand by (735 - 2816)
kW
1008
1076
Prime power (536 - 2044)
Stand by (588 - 2253)
Stand by (588 - 2253)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
459,20
Width (B)
220
High (C)
239,80
Long (A)
180,79
Width (B)
86,61
High (C)
94,41
Weight
Weight with liquid in radiator and carter
9.550 21.057,75
9.550 21.057,75
Fuel capacity
0