HGO-70 M6 NG
64 kVA Generator set Open Skid
Powered by: FORD
Alternator: STAMFORD
Single phase | 60 Hz | Natural Gas |
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 77kW prp ; 86kW standby
- Manufacturer: FORD
- Model: WSG873
- Engine Type: 4-stroke Otto Cycle
- Injection Type: Carburization
- Aspiration Type: Natural
- Number of cylinders and arrangement: 8-V
- Bore and Stroke: 107,2 x 101 mm
- Displacement: 7,3 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: API ≥SM, SAE 5W30
- Compression Ratio: 10,5
- Fuel Consumption 80 % PRP: 830.49 cfh
- Total oil capacity including tubes, filters 7,5 L
- Governor Type Electrical
- Air Filter Type Dry
- Natural Gas engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: UCI274C
- Poles: 4
- Connection type (standard): Double delta
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Steel industrial silencer -15db(A) attenuation
- Steel residential silencer -35db(A) attenuation. (Optional)
- - GAS RAMP.
- Gas filter
- Double solenoid valve
- High pressure regulator
- Low pressure switch
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- High pressure switch (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Exhaust Gas Flow: 17 m3/min
- Maximum allowed back pressure: 20,32 kPa
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 335,07 m3/h
- Alternator fan air flow: 0,617 m3/s
- - STARTING SYSTEM.
- - FUEL SYSTEM
- Fuel Oil Specifications: Natural Gas
- - DIMENSIONS.
- Length: 2.100 mm
- Height: 1.650 mm
- Width: 900 mm
- Maximum shipping volume: 3,12 m3
- Weight with liquids in radiator and sump: 1.144 kg
Power
kVA
64
72
Prime power (22 - 97)
Stand by (24 - 108)
Stand by (24 - 108)
kW
64
72
Prime power (18.1 - 77)
Stand by (19.8 - 86)
Stand by (19.8 - 86)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
210
Width (B)
90
High (C)
165
Long (A)
82,68
Width (B)
35,43
High (C)
64,96
Weight
Weight with liquid in radiator and carter
1.144 2.522,52
1.144 2.522,52
Fuel capacity
0