HSW-610 T5
613 kVA Generator set Open Skid
Powered by: SCANIA
Alternator: MECC ALTE
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 516kW prp ; 569kW standby
- Manufacturer: SCANIA
- Model: DC16-93A(02-53)
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 90º V8
- Bore and Stroke: 130 x 154 mm
- Displacement: 16,4 L
- Cooling System: Coolant
- Lube Oil Specifications: ACEA E3,E4,E5 or E7
- Compression Ratio: 16,7:1
- Fuel Consumption ESP: 131 l/h
- Fuel Consumption 100% PRP: 115,8 l/h
- Fuel Consumption 75 % PRP: 85,1 l/h
- Fuel Consumption 50 % PRP: 58,2 l/h
- Lube oil consumption with full load: 0,2
- Total oil capacity: 48 L
- Total coolant capacity: 68 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO40.2L4C
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 552 ºC
- Exhaust Gas Flow: 0,733 kg/s
- Maximum allowed back pressure: 100 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 2128,4 m3/h
- Cooling Air Flow: 16,1 m3/s
- Alternator fan air flow: 0,9 m3/s
- - STARTING SYSTEM.
- Starting power: 7 kW
- Starting power: 9,52 CV
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 740 L
- - DIMENSIONS.
- Length: 3.600 mm
- Height: 2.096 mm
- Width: 1.460 mm
- Maximum shipping volume: 11,02 m3
- Weight with liquids in radiator and sump: 3.495 kg
- Fuel tank capacity: 740 L
- Autonomy: 9 Hours
Power
kVA
613
674
Prime power (250 - 735)
Stand by (275 - 807)
Stand by (275 - 807)
kW
490
539
Prime power (200 - 588)
Stand by (220 - 646)
Stand by (220 - 646)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
360
Width (B)
146
High (C)
209,60
Long (A)
141,73
Width (B)
57,48
High (C)
82,52
Weight
Weight with liquid in radiator and carter
3.495 7.706,48
3.495 7.706,48
Fuel capacity
740
195,36