HFW-245 T5
250 kVA Generator set Open Skid
Powered by: FPT_IVECO
Alternator: MECC ALTE
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 216,1kW prp ; 238,3kW standby
- Manufacturer: FPT_IVECO
- Model: N67.TE8P
- Engine Type: 4-stroke diesel
- Injection Type: Direct, common rail
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 104 x 132 mm
- Displacement: 6,7 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: 10W-40 (API CJ-4, CK-4)
- Compression Ratio: 17:1
- Fuel Consumption ESP: 59,7 l/h
- Fuel Consumption 100% PRP: 52,4 l/h
- Fuel Consumption 80 % PRP: 41,3 l/h
- Fuel Consumption 50 % PRP: 25,7 l/h
- Fuel Consumption 25 % PRP: 14,4 l/h
- Lube oil consumption with full load: 0,3 % of fuel consumption
- Total oil capacity including tubes, filters 17 L
- Total coolant capacity: 27,6 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO38.2M4C
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- High mechanical strength
- Epoxy polyester powder coating
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum allowed back pressure: 20 kPa
- Heat dissipated by exhaust pipe: 560 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 775,6 m3/h
- Cooling Air Flow: 3,97 m3/s
- Alternator fan air flow: 0,533 m3/s
- - STARTING SYSTEM.
- Recommended battery: 50 x 2 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 449 L
- - DIMENSIONS.
- Length: 3.000 mm
- Height: 1.640 mm
- Width: 1.160 mm
- Maximum shipping volume: 5,71 m3
- Weight with liquids in radiator and sump: 1.810 kg
- Fuel tank capacity: 449 L
- Autonomy: 11 Hours
Power
kVA
250
275
Prime power (53 - 625)
Stand by (58 - 690)
Stand by (58 - 690)
kW
200
220
Prime power (42 - 500)
Stand by (46 - 552)
Stand by (46 - 552)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
300
Width (B)
116
High (C)
164
Long (A)
118,11
Width (B)
45,67
High (C)
64,57
Weight
Weight with liquid in radiator and carter
1.810 3.991,05
1.810 3.991,05
Fuel capacity
449
118,54