HFW-310 T5
301 kVA Generator set Open Skid
Powered by: FPT_IVECO
Alternator: STAMFORD
Three phase | 50 Hz | Diesel | Stage 3A
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 206,3kW cop ; 259,3kW prp ; 286,3kW standby
- Manufacturer: FPT_IVECO
- Model: C87TE1PV
- Engine Type: 4-stroke diesel
- Injection Type: Direct, common rail
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 117 x 135 mm
- Displacement: 8,7 L
- Cooling System: Coolant
- Lube Oil Specifications: SAE 15 W40
- Compression Ratio: 16,5:1
- Fuel Consumption ESP: 72,8 l/h
- Fuel Consumption 100% PRP: 68,6 l/h
- Fuel Consumption 80 % PRP: 59,2 l/h
- Fuel Consumption 50 % PRP: 34,5 l/h
- Fuel Consumption 25 % PRP: 18,2 l/h
- Lube oil consumption with full load: 0,25 % of fuel consumption
- Total oil capacity including tubes, filters 28 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: S4L1D.D41
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- High mechanical strength
- Epoxy polyester powder coating
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 723 ºC
- Exhaust Gas Flow: 0,357 kg/s
- Maximum allowed back pressure: 7 kPa
- - NECESSARY AMOUNT OF AIR.
- Alternator fan air flow: 0,83 m3/s
- - STARTING SYSTEM.
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 449 L
- - DIMENSIONS.
- Length: 3.000 mm
- Height: 1.790 mm
- Width: 1.160 mm
- Maximum shipping volume: 6,23 m3
- Weight with liquids in radiator and sump: 2.542 kg
- Fuel tank capacity: 449 L
- Autonomy: 8 Hours
Power
kVA
301
330
Prime power (53 - 625)
Stand by (58 - 690)
Stand by (58 - 690)
kW
241
264
Prime power (42 - 500)
Stand by (46 - 552)
Stand by (46 - 552)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
300
Width (B)
116
High (C)
179
Long (A)
118,11
Width (B)
45,67
High (C)
70,47
Weight
Weight with liquid in radiator and carter
2.542 5.605,11
2.542 5.605,11
Fuel capacity
449
118,54